WORLD CLASS 3000 COMBUSTION FLUE GAS ANALYZERS
World Class 3000 In-situ Oxygen Analyzer Packages

Data Sheet

The Hagan in situ, zirconium oxide oxygen analyzer has long been established as the industry standard. The leader in oxygen flue gas analyzer technology, Rosemount Analytical has combined this Hagan expertise with state of the art features into one package - the World Class 3000 Oxygen Analyzer.

The World Class 3000 is completely field repairable as internal components are conveniently accessible for in-house service personnel. For example, the heater/thermocouple probe assembly can be replaced and returned to service by in-house personnel in one-half hour or less. This repair is made without requiring the probe tube to be removed from the process.

The World Class 3000 Analyzer offers flexible, microprocessor-based electronics configurations with the following components: IFT 3000 Intelligent Field Transmitter, HART® Model 275 Hand-Held Interface, MPS 3000 Multiprobe Test Gas Sequencer, CRE 3000 Control Room Electronics, HPS 3000 Field Interface Module.
The HART® communications protocol allows instrument technicians to interface with the probe’s IFT 3000 Intelligent Field Electronics from the control room or any location where the 4-20 mA signal wires terminate. Service diagnostics and calibrations can be performed without requiring plant personnel to enter the often hot, inaccessible probe location.

Calibration data indicates the condition of the zirconium oxide sensor cell. Analyzer calibration requires no special equipment or knowledge and can be fully automated by incorporating the MPS 3000 Multiprobe Test Gas Sequencer. Cost is minimized and expansion is easy as the Multiprobe Test Gas Sequencer is a modular design for one to four World Class 3000 probes.

Rosemount Analytical also offers World Class 3000 Oxygen Analyzer packages suitable for operation in hazardous area locations (ie CENELEC EEXd.). Please refer to product data sheet PD-106-300NX for more information.

A World Class 3000 analyzer package typically includes an oxygen sensing probe, signal conditioning electronics and these optional accessories: mounting hardware, reference air set, calibration gas rotometer and up to 150 feet of cable.

The IFT 3000 Intelligent Field Transmitter provides a user interface, signal conditioning, diagnostics and calibration for single probe applications. For applications where multiple oxygen analyzers are installed on site, Rosemount Analytical offers a multiprobe system. Up to eight (8) oxygen probes can be connected to one OxyBalance Electronics. Either of these electronics configurations provide semi automatic calibration without requiring manual potentiometer adjustments. Additionally, the optional MPS 3000 Multiprobe Test Gas Sequencer provides fully automatic calibration by automatically introducing calibration gases.
The HPS 3000 Heater Power Supply permits the probe heater to be powered locally, eliminating lengthy runs of heavy-gauge power wiring between the field electronics and the probe.

The IFT 3000 Intelligent Field Transmitter is shipped from the factory pre-set for 4-20 mA output representing 0 to 10% oxygen and alarm indication of fault conditions including high/low O2 alarms with 3 relay outputs. Various other output signals and oxygen ranges are field selectable.

The IFT 3000 electronics are housed in a standard NEMA 4X (IP65) enclosure for full weatherproof and corrosion protection. The deluxe version has a large easy-to-read LED display for percent oxygen readout. A membrane keypad with a 4 x 20 character LCD display provides an easy-to-use interface for setting operating parameters and for viewing process and diagnostic data. When used with a stack thermocouple, stack temperatures and percent combustion efficiency are obtained. Manual, automatic and remote initiation of calibration are also available.

The IFT 3000 electronics are also available in a low-cost configurations with no LCD display or keypad. Both versions can be accessed via the Rosemount Model 275 Hand-Held Interface. The HART® Field Communications Protocol permits all operator functions to also be performed from the control room, utilizing the same twisted pair of wires that carry the 4-20 mA output signal. The Rosemount Model 275 Hand-Held Interface permits operator interface into the IFT 3000 Electronics from anywhere the 4-20 mA signal terminates.
EXCHANGE/UPGRADE of EXISTING OXYGEN ANALYZER UTILIZING EXISTING ELECTRONICS

Upgrade your old oxygen analysis system with the World Class 3000 Oxygen Analyzer. The World Class 3000 probe may be operated using older existing Westinghous/Hagan, Rosemount Analytical or selected competitive electronics. Rosemount analytical will offer a credit for existing probes shipped to our factory.

3001DR Direct Replacement Model

Or

3001NE Exchange Model (utilizes extended life 44V heater with HPS 3000 module)
Accessories
O2 Test Gas Kit

Data Sheet

Emerson’s Rosemount Analytical Oxygen Test Gas and Service Kits have been carefully designed to provide a more convenient and fully portable means of testing, calibrating and servicing Rosemount Analytical oxygen analyzers. These lightweight, disposable gas cylinders eliminate the need to rent test gas bottles.
MPS 3000 Multi-probe Gas Sequencer

Data Sheet

This package allows for up to four remote calibration sequencing with a maximum distance of 300’ from the probe.
Accessories for High Temperature Operation
Bypass Packages

Data Sheet

The specially designed Rosemount analytical Bypass Package for oxygen analyzers has proven to withstand the high temperatures in process heaters while providing the same advantages offered by the in-situ sensor. Inconel or Kanthal steel tubes provide effective resistance to corrosion and the package uses no moving parts, air pumps or other components common to other sampling systems
High Temperature Probe Jackets

Data Sheet

Emerson’s Rosemount Analytical patented in-situ probe mounting jackets enable oxygen analyzers to operate in temperatures up to 2000°F (1093°C) in processes such as process heaters, incinerators and steam generators while providing all of the advantages offered by the in-situ zirconium oxide sensor. Ideal for high particulate applications, these jackets protect the probe from harmful flue gas concentration and use no moving parts or pumps. All components in contact with the process are constructed of high temperature tolerant stainless steel.
Oxymitter In-Situ Flue Gas Oxygen Transmitter

Data Sheet